Medical Gas Inspection Service
  Leave Feedback
Name Your Test Price
Email Address:
Password:
 

Forgot your password?   |   Create an account »

   
This auction ended on August 19, 2016 @ 12:00 AM EDT

Medical Gas Inspection Service

Listed By: sales     No ratings yet   View rating history and comments

Auction Description

Specific Information about this Opportunity:

Statement of Work - Annual Medical Gas Inspection

Annual Evaluation of the piped OXYGEN, NITROUS OXIDE, MEDICAL AIR, DENTAL AIR, MEDICAL VACUUM, DENTAL VACUUM, NITROGEN and EVACUATION/WAGD Systems, in accordance with JCAHO (Joint Commission on Accreditation of Healthcare Organizations) 2016 standards, CGA (Compressed Gas Association) standards, NFPA 99 (National Fire Protection Association) 2015 standards, ASSE (American Society of Sanitary Engineering 6000, 2006), and USP/NF (United States Pharmacopeia Convention) requirements and recommendations. All equipment is located on the Dayton VAMC Campus located at 4100 West 3rd Street, Dayton OH 45428. All work shall be completed by September 30, 2016 and a written report shall be provided within 30 days after on site work. The report shall include all findings, note what was checked and the location, and reference applicable code sections. The report shall also provide a concise listing of discrepancies for inlet/outlets, alarm panels, source equipment, and zone valves (example provided below); this concise listing shall provide location (building and floor), room number, discrepancy, NFPA code that discrepancy applies to, recommended resolution for discrepancy, and any additional notes. Deficiencies noted shall be communicated to the COR within 24 hours of discovery and include a recommendation for remediation. The contractor should provide adequate staff to monitor up to 3 master alarm panels and sources when checking the source alarms (minimum of 4 contractors needed). The contractor may have to work outside the usual hours of 7am-4:30pm due to clinical need in some areas such as surgery, recovery room, GI clinic and emergency department. Work shall be coordinated with Biomedical Engineering. Inspection shall include checking of all source valves. The VA will provide a technician to accompany the contractor when checking source valves. Contractor shall check ALL outlets/inlets, skipping those in use and noting them on the report. All bidders must be certified to inspect medical gas systems and shall include a copy of the certification with their final report.

Example of discrepancy listing for report:

Location Room Discrepancy NFPA Note Recommended ResolutionInclude Building and floor Room# Description of the discrepancy NFPA code that discrepancy applies to Additional notes The recommended resolution for discrepancyBldg. 330, 3 South 3D101 Oxygen outlet is leaking while in use NFPA 99… Replace O-rings

Systems, approximate outlet count, and equipment to be inspected include: Medical Gas Sources - Bldg. 330, Bldg. 310, Bldg. 320, and Bldg. 315 Oxygen - 2 Bulk SitesMedical Air - 4 Compressor SetsVacuum - 5 Compressor SetsNitrous Oxide - 2 ManifoldsNitrogen - 2 Manifold

Dental Air Tower - 1 Compressor set

Zone Valve Shutoffs Tower Complex - 192 Bldg. 320 - 4 Bldg. 315 - 3

Zone Warning Alarm Panels Tower Complex - 108 Bldg. 315 - 2

Master Alarm Panels Tower Complex - 3 Bldg. 320 - 2

Medical Gas Outlets -Tower Complex (Building 330, 310, 315)Oxygen - 562 Medical Air - 563 Vacuum - 666 EVAC - 2 Nitrous Oxide - 17 Nitrogen - 10CO - 2CO2 - 2

Medical Gas Outlets - Bldg. 320 Oxygen - 40 Vacuum - 40 Medical Air - 40

Performance of JCAHO 2016 and NFPA 99 2015 required testing includes but is not limited to the following:*Note - Where states to check for brazing, labeling, hanging, etc. it is not expected for the contractor to lift every ceiling type but to inspect these items where there are no ceiling tiles (such as mechanical rooms). Please note that ceiling tiles will have to be removed to test pressure switches.

MEDICAL OXYGEN SYSTEM" Tested area alarms for proper pressure switch location and alarm function.

" Tested Oxygen system for concentration and gaseous purity at each outlet.

" Tested Oxygen for particulate contamination at least once in each zone. o Tested with 0.45 micron filter device.

" Tested Oxygen system for pressure at each zone.

" Tested each Oxygen outlet for proper function, identification, adaptation and mechanical integrity. o Identified leaking/malfunctioning outlets o Identified outlets delivering substandard pressure/flow rates " Tested Oxygen zone shut-off valves for proper function, identification and mechanical integrity. " Checked Oxygen pipeline for proper identification labeling." Tested each zone for available flow. " Tested operational pressure tests at each station outlet/inlet " Tested each critical care outlet operational pressure test o Tested outlet flow rate and pressure drop with high demand at adjacent outlets.

" Tested Oxygen system components for leakage.

" Checked Oxygen system components for proper installation (i.e.: Brazing, Labeling, Hanging, etc.)

" Checked for crossed lines.

MEDICAL AIR SYSTEM" Tested area alarms for proper pressure switch location and alarm function.

" Tested Medical Air system gaseous purity. (Oxygen Concentration, Gaseous Hydrocarbons, Liquid Hydrocarbons, Carbon Monoxide, Carbon Dioxide, etc.). o Tested at source sample valve. o Tested Medical Air for particulate contamination at least once in each zone. o Tested with 0.45 micron filter device

" Tested source for dew point.

" Tested medical Air System for pressure at each zone.

" Tested each Medical Air outlet for proper function, identification, adaptation, and mechanical integrity.o Identified leaking/malfunctioning outlets o Identified outlets delivering substandard pressure/flow rates

" Tested Medical Air zone shut-off valves for proper function, identification, and mechanical integrity.

" Checked Medical Air pipeline for proper identification labeling

" Tested each zone for available flow.

" Tested operational pressure tests at each station outlet/inlet

" Tested each critical care outlet operational pressure test. o Tested outlet flow rate and pressure drop with high demand at adjacent outlets

" Tested Medical Air System components for leakage.

" Checked Medical Air system components for proper installation (i.e.: Brazing, Labeling, Hanging, etc.)

" Checked for crossed lines.

MEDICAL SURGICAL VACUUM SYSTEM" Tested area alarms for proper pressure switch location and alarm function

" Tested each Vacuum inlet for available flow rate SCFM

" Tested operational pressure tests at each station outlet/inlet

o Tested each Vacuum inlet for proper function, identification, adaptation, and mechanical integrity. o Identified leaking/malfunctioning inlets o Identified inlets delivering substandard vacuum/flow rate

" Tested all Vacuum zone valves for proper function, identification, and mechanical integrity

" Checked Vacuum system components for proper installation (i.e.: Brazing, Labeling, Hanging, etc.).

" Checked for crossed lines.

NITROGEN SYSTEM" Tested area alarms for proper pressure switch location and alarm functiono Tested Nitrogen system for particulate contamination. o Tested with 0.45 micron filter device

" Tested Nitrogen system for pressure at each zone.

" Tested Nitrogen system outlets for proper function, identification, adaptation, and mechanical integrity.o Identified leaking/malfunctioning outlets o Identified outlets delivering substandard pressure/flow rate " Tested Nitrogen zone shut-off valve for proper function, identification, and mechanical integrity. " Checked Nitrogen pipeline for proper identification labeling." Tested Nitrogen control panels for leakage and proper operation. " Checked Nitrogen system components for proper installation (i.e.: Brazing, Labeling, Hanging, etc.)" Checked for crossed lines." Check flexible connectors.NITROUS OXIDE SYSTEM" Tested area alarms for proper pressure switch location and alarm function

" Tested Nitrous Oxide system for concentrationo Tested Nitrous Oxide system for particulate contamination. o Tested with 0.45 micron filter device

" Tested Nitrous Oxide system for pressure at each zone.

" Tested each Nitrous Oxide outlet for proper function, identification, adaptation, and mechanical integrity. o Identified leaking/malfunctioning outlets o Identified outlets delivering substandard pressure/flow rates

" Tested Nitrous Oxide zone shut-off valves for proper function, identification, and mechanical integrity.

" Checked Nitrous Oxide pipeline for proper identification labeling.

" Tested each Nitrous Oxide outlet for available flow.

" Tested Nitrous Oxide pipeline components for leakage.

" Checked Nitrous Oxide system components for proper installation (i.e.: Brazing, Labeling, - Hanging, etc.)

" Checked for crossed lines.

" Check flexible connectors.

DENTAL AIR SYSTEM" Tested Dental Air system for pressure

" Tested Dental Air zone shut-off valves for proper function, identification, and mechanical integrity. " Checked Dental Air system components for proper installation (i.e.: Brazing, Labeling, Hanging, etc.).

" Checked for crossed lines

EVACUATION/WAGD" Tested area alarms for proper pressure switch location and alarm function

" Tested inches (of mercury) of E-VAC at each zone

" Tested each E-VAC inlet for available flow rate SCFM.o Tested pressure at each inlet in all critical care areas. o Tested for flow rate and pressure drop with high volume demand on adjacent inlets " Tested each E- V AC inlet for proper function, identification, adaptation, and mechanical integrity. o Identified leaking/malfunctioning inlets o Identified inlets delivering substandard vacuum/flow rate

" Tested all E-VAC zone valves for proper function, identification, and mechanical integrity

" Checked E-VAC system components for proper installation (i.e.: Brazing, Labeling, Hanging, etc.).

" Checked for crossed lines.

DENTAL VACUUM SYSTEM" Checked Dental Vacuum system components for proper installation (i.e.: Brazing, Labeling, Hanging, etc.).

" Checked for crossed lines.

Auction Timeframe

Available for Start
At auctions end
Required Completion
At auctions end

Categories

Gas Testing
Inspection Services
Medical Equipment Testing

Accreditations

No specific accreditations required

Questions/Comments

No questions or comments found

Russia Area Approvals Made Simple - CISCERT - Visit ciscert.com to learn more. First 10 customers that mention they saw this ad on NameYourTestPrice.com receive their certificates at no cost. Testing, shipping samples and government fees are extra.
Connect With Us On

Get connected to the latest industry news and information. Sign up now and access expanded search results, review suppliers, post or bid on projects, receive industry specific news and opportunities– and more!

Facebook Icon Google Plus Icon Twitter Icon LinkedIn Icon
Testimonials

"When we had a need to add additional capacity to our product certification team the service we chose was Name Your Test Price. They assisted in the scoping of the work, they located a lab that could provide the quickest turnaround time and liaised with the lab to help define our expectations. Name Your Test Price response to questions was extremely quick and their insight on laboratory procedures was excellent. I plan to use Name Your Test Price again in the future."

-Kevin Flanders, UTC Fire & Security Americas Corporation, Inc.

"I was searching for labs in the States who tested consumer products. I was unsure of where to go and how to get started. So many labs! The field was vast and overwhelming. I spoke to NameYourTestPrice.com and they understood what I needed and made excellent suggestions and provided me with helpful contacts. Thanks Name Your Test Price!"

-Maggie Gilmour, Researcher, Discovery Channel - Toronto Ontario

"When we had a need to conduct some external testing, we started by contacting local testing labs and got quotes of $500 per sample. Then we found testing partners and they were able to get the job done for $200 per sample, saving us thousands! We have been working with them for our external testing and certification needs ever since."

Nathan Isser, Ph.D., Lawter - Director of Innovation